欢迎光临康明斯动力设备(深圳)有限公司官网!
  • 静音发电机组|低噪音发电机组|康明斯发电方舱|移动电站

康明斯动力设备(深圳)有限公司

康明斯客户服务热线

13600443583
  • 技术参数
    当前位置:首页 > 技术标准 > 柴油机标准
    柴油机标准 / 康明斯发动机参数

    1120KW康明斯静音柴油机性能参数曲线图(英文版)

    Date: 2020-04-11Hits:
    导读:Basic Engine Model: KTA50-G3 Curve Number:FR-6250 Page No.
    Engine Critical Parts List: CPL: 2227 Date:12Jan01
    Displacement : 50.3 litre (3067 in3 ) Bore : 159 mm (6.25 in.) Stroke : 159 mm (6.25 in.)
    ...

     

    图片5.png                         UMMINS ENGINE COMPANY, INC
                                  Columbus, Indiana 47201
                             ENGINE  PERFORMANCE CURVE
     
    Basic Engine Model: KTA50-G3      Curve Number:FR-6250        Page No.
    Engine Critical Parts List: CPL: 2227   Date:12Jan01
    Displacement : 50.3 litre (3067 in3 )  Bore : 159 mm (6.25 in.)       Stroke : 159 mm (6.25 in.)
    No. of Cylinders : 16       Aspiration : Turbocharged and Aftercooled
       Engine Speed    Standby Power Rating  Prime Power Rating  Continuous Power Rating
                                             Limited TimeUnlimited Time
    RPM        kWmBHP   kWm     BHP    kWmBHP  kWmBHP1500     1227 1645   1150      1541    1097 1470   900 1206
    1800     1380 1850   1300      1742    1220 1635   1000 1340
    Engine Performance Data @ 1500 RPM
    OUTPUT POWER          FUEL CONSUMPTION
    %  kWm  BHP kg/kWm·h  lb/BHP·h  litre/hour  U.S. Gal/hour
    图片4.png
    STANDBY POWER
    100 1227  1645  0.203   0.334 293      77.4
    PRIME -- LIMITED TIME RUNNING POWER
    100 1150  1541  0.202   0.333 274      72.3
    PRIME  -- UNLIMITED TIME RUNNING POWER
    100 1097  1470  0.202   0.333 261      69.0
     75  822  1102  0.206   0.338 199      52.5
     50  548   735  0.216   0.355 139      36.6
     25  275   368  0.234   0.385  76      20.0
    CONTINUOUS POWER
    100   900 1206 0.204   0.336  216   57.1
     
     
     
     
     
     
     
    CONVERSIONS:(Litres = U.S. Gal x 3.785)(kWm = BHP x 0.746) (U.S. Gal = Litres x 0.2642)  (BHP = Engine kWm x 1.34)
     
    These guidelines have been formulated to ensure proper application of generator drive engines in A.C. generator set installations. Generator drive engines are not designed for and shall not be used in variable speed D.C. generator set applications.
    STANDBY POWER RATING
    Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. Under no condition is an engine allowed to operate in parallel with the public utility at the Standby Power rating. This rating should be applied where reliable utility power is available. A Standby rated engine should be sized for a maximum of an 80% average load factor and 200 hours of operation per year. This includes less than 25 hours per year at the Standby Power rating. Standby ratings should never be applied except in true emergency power outages. Negotiated power outages contracted with a utility company are not considered an emergency.
     
    PRIME POWER RATING
    Applicable for supplying electric power in lieu of commercially purchased power. Prime Power applications must be in the form of one of the following two categories:
    UNLIMITED TIME RUNNING PRIME POWER
    Prime Power is available for an unlimited number of hours per year in a variable load application. Variable load should not exceed a 70% average of the Prime Power rating during any operating period of 250 hours. The total operating time at 100% Prime Power shall not exceed 500 hours per year. A 10% overload capability is available for a period of 1 hour within a 12-hour period of operation. Total operating time at the 10% overload power shall not exceed 25 hours per year.
     
    LIMITED TIME RUNNING PRIME POWER
    Limited Time Prime Power is available for a limited number of hours in a non-variable load application. It is intended for use in situations where power outages are contracted, such as in utility power curtailment. Engines may be operated in parallel to the public utility up to 750 hours per year at power levels never to exceed the Prime Power rating. The customer should be aware, however, that the life of any engine will be reduced by this constant high load operation. Any operation exceeding 750 hours per year at the Limited Time Prime Power rating should use the Continuous Power rating.
     
    CONTINUOUS POWER RATING
    Applicable for supplying utility power at a constant 100% load for an unlimited number of hours per year. No overload capability is available for this rating.
     
    Data shown above represent gross engine performance capabilities obtained and corrected in accordance with ISO-3046 conditions of 100 kPa (29.5 in Hg) barometric pressure [110 m (361 ft) altitude], 25 °C (77 °F) air inlet temperature, and relative humidity of 30% with No. 2 diesel or a fuel corresponding to ASTM D2.
    See reverse side for application rating guidelines.
    The fuel consumption data is based on No. 2 diesel fuel weight at 0.85 kg/litre (7.1 lbs/U.S. gal).
    Power output curves are based on the engine operating with fuel system, water pump and lubricating oil pump; not included are battery charging alternator, fan, optional equipment and driven components.
                                                      图片3.png      
    TECHNICAL DATA DEPT.            CERTIFIED WITHIN 5%               CHIEF ENGINEER
     
     
     
     Engine Speed    Standby Power Rating  Prime Power Rating  Continuous Power Rating
                                           Limited Time    Unlimited Time
    RPM        kWmBHP   kWm     BHP   kWm BHP  kWmBHP 1500     1227 1645   1150   1541 1097  1470   900 1206
    1800     1380 1850   1300   1742 1220  1635   1000 1340
     
    Engine Performance Data @ 1800 RPM
    OUTPUT POWER          FUEL CONSUMPTION
    %  kWm  BHP kg/kWm·h  lb/BHP·h  litre/hour  U.S. Gal/hour
    STANDBY POWER
    100 1380  1850  0.204   0.335 330       87.3
    PRIME -- LIMITED TIME RUNNING POWER
    100 1300  1742  0.203   0.334 310       81.0
    PRIME  -- UNLIMITED TIME RUNNING POWER
    100 1220  1635  0.203   0.334 291     76.9
     75  915  1226  0.207   0.340 222       58.7
     50  610   818  0.220   0.361 157       41.6
     25  305   409  0.249   0.410  89       23.6
    CONTINUOUS POWER
    100 1000  1340  0.206   0.338 242       63.8
     
    CONVERSIONS:(Litres = U.S. Gal x 3.785)(kWm = BHP x 0.746)  (U.S. Gal = Litres x 0.2642)  (BHP = Engine kWm x 1.34)
     
    These guidelines have been formulated to ensure proper application of generator drive engines in A.C. generator set installations. Generator drive engines are not designed for and shall not be used in variable speed D.C. generator set applications.
     
    STANDBY POWER RATING
    Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. Under no condition is an engine allowed to operate in parallel with the public utility at the Standby Power rating. This rating should be applied where reliable utility power is available. A Standby rated engine should be sized for a maximum of an 80% average load factor and 200 hours of operation per year. This includes less than 25 hours per year at the Standby Power rating. Standby ratings should never be applied except in true emergency power outages. Negotiated power outages contracted with a utility company are not considered an emergency.
     
    PRIME POWER RATING
    Applicable for supplying electric power in lieu of commercially purchased power. Prime Power applications must be in the form of one of the following two categories:
     
    UNLIMITED TIME RUNNING PRIME POWER
    Prime Power is available for an unlimited number of hours per year in a variable load application. Variable load should not exceed a 70% average of the Prime Power rating during any operating period of 250 hours. The total operating time at 100% Prime Power shall not exceed 500 hours per year. A 10% overload capability is available for a period of 1 hour within a 12-hour period of operation. Total operating time at the 10% overload power shall not exceed 25 hours per year.
     
    LIMITED TIME RUNNING PRIME POWER
    Limited Time Prime Power is available for a limited number of hours in a non-variable load application. It is intended for use in situations where power outages are contracted, such as in utility power curtailment. Engines may be operated in parallel to the public utility up to 750 hours per year at power levels never to exceed the Prime Power rating. The customer should be aware, however, that the life of any engine will be reduced by this constant high load operation. Any operation exceeding 750 hours per year at the Limited Time Prime Power rating should use the Continuous Power rating.
     
    CONTINUOUS POWER RATING
    Applicable for supplying utility power at a constant 100% load for an unlimited number of hours per year. No overload capability is available for this rating.
     
    Data shown above represent gross engine performance capabilities obtained and corrected in accordance with ISO-3046 conditions of 100 kPa (29.5 in Hg) barometric pressure [110 m (361 ft.) altitude], 25 °C (77 °F) air inlet temperature, and relative humidity of 30% with No. 2 diesel or a fuel corresponding to ASTM D2.
    See reverse side for application rating guidelines.
    The fuel consumption data is based on No. 2 diesel fuel weight at 0.85 kg/litre (7.1 lbs/U.S. gal).
    Power output curves are based on the engine operating with fuel system, water pump and lubricating oil pump; not included are battery charging alternator, fan, optional equipment and driven components.
     
    图片3.png 
     
    TECHNICAL DATA DEPT.       CERTIFIED WITHIN 5%                CHIEF ENGINEER
     
     
                KTA50-G3 Derate Curves @ 1500 RPM       CURVE NO : FR-6250
    图片2.png          
                   
     
     
                                                            DATE : 12Jan01
     
     
     
        NOTE: Derates shown are based on 15 in H20 air intake restriction and 2 in Hg exhaust back pressure.
        For sustained operation above these conditions, derate by an additional 5% per 1000 ft (300 m) and 9% per 18° F (10°
     
               Reference Standards:
                    BS-5514 and DIN-6271 standards are based on ISO-3046.
     
     
                               Cummins Engine Company, Inc.
                             Engine Data Sheet
                                                                             DATA SHEET : DS-6250
    ENGINE MODEL :  KTA50-G3    CONFIGURATION NUMBER : D283021DX02      DATE : 12Jan01               
                                                                ERFORMANCE CURVE : FR-6250
    INSTALLATION DIAGRAM                CPL NUMBER
    • Fan to Flywheel 3626420                 • Engine Critical Parts List :   2227
     
    GENERAL ENGINE DATA
    Type .........................................................................................................................................................   4-Cycle; 60° Vee; 16-Cylinder Diesel
    Aspiration .................................................................................................................................................   Turbocharged and Aftercooled
    Bore x Stroke.........................................................................................................—  in x in (mm x mm)   6.25 x 6.25 (159 x 159)
    Displacement. ......................................................................................................................—  in3 (liter)   3067 (50.3)
    Compression Ratio....................................................................................................................................   13.9 : 1
    Dry Weight
        Fan to Flywheel Engine.........................................................................................................—lb (kg)          11820          (5360)
        Heat Exchanger Cooled Engine............................................................................................—lb (kg)          12260          (5560)
    Wet Weight
    Fan to Flywheel Engine.........................................................................................................—lb (kg)          12485          (5662)
    Heat Exchanger Cooled Engine ......................................................................................... .—lb (kg)        13085          (5934)
    Moment of Inertia of Rotating Components
    • with FW 6009 Flywheel ...........................................................................................—lbm• ft2(kg • m2)            301        (12.7)
    • with FW 6017 Flywheel. ........................................................................................—lbm • ft2 (kg • m2)          515           (21.7)
    Center of Gravity from Rear Face of Flywheel Housing (FH 6024)..............................................—in (mm)          47.5           (1206)
    Center of Gravity Above Crankshaft Centerline ...........................................................................—in (mm)           11.0         (279)
    Maximum Static Loading at Rear Main Bearing..............................................................................—lb (kg)         2000            (908)
    ENGINE MOUNTING
          Maximum Bending Moment at Rear Face of Block .................................................—lb • ft (N • m)         4500         (6100)
    EXHAUST SYSTEM
          Maximum Back Pressure @ Standby Power Rating.................................................—in Hg (mm Hg)             2             (51)
    AIR INDUCTION SYSTEM
    Maximum Intake Air Restriction
    • with Dirty Filter Element @ Standby Power Rating .....................................................—in H2O (mm H2O)            25           (635)
    • with Clean Filter Element @ Standby Power Rating ...................................................—in H2O (mm H2O)            15           (381)
    COOLING SYSTEM 
    Coolant Capacity  —  Engine Only .......................................................................................—US gal (liter)          42.5           (161)
    Maximum Coolant Friction Head External to Engine —1800 rpm...............................................—psi (kPa)             15           (103)
                                              —1500 rpm...............................................—psi (kPa)             10            (69)
    Maximum Static Head of Coolant Above Engine Crank Centerline...................................................— ft (m)              60          (18.3)
    Standard Thermostat (Modulating) Range....................................................................................... —°F (°C)       180 - 200     (82 - 93)
    Minimum Pressure Cap (For Cooling Systems with less than 2 m [6 ft.] Static Head)....................—psi (kPa)            14         (96)
    Maximum Top Tank Temperature for Standby / Prime Power ...........................................................—°F (°C)       220 / 21       (104 / 100)
    LUBRICATION SYSTEM
    Oil Pressure  @ Idle Speed ...........................................................................................................—psi (kPa)            20           (138)
                 @ Governed Speed .................................................................................................—psi (kPa)           50 - 70      (345 - 483)
    Maximum Oil Temperature.................................................................................................................—°F (°C)           250           (121)
    Oil Capacity with OP 6024 Oil Pan : High - Low .......................................................................—US gal (liter)       40 - 32       (151 - 121)
    Total System Capacity (Including Bypass Filter).......................................................................—US gal (liter)         46.7             (177)
    Angularity of OP 6024 Oil Pan —Front Down .........................................................................................         30°
                              —Front Up ..............................................................................................         30°
                              —Side to Side.........................................................................................          30°
    FUEL SYSTEM
    Type Injection ............................................................................................................................................................Direct Injection Cummins PT
     
    Maximum Restriction at PT Fuel Injection Pump —with Clean Fuel Filter................................................—in Hg (mm Hg)   4.0      (102)
                                               —with Dirty Fuel Filter...................................................—in Hg (mm Hg)   8.0      (203)
    Maximum Allowable Head on Injector Return Line (Consisting of Friction Head and Static Head)..........—in Hg (mm Hg)   6.5     (165)
    Maximum Fuel Flow to Injection Pump................................................................................................— US gph (liter / hr)  165      (625)
    ELECTRICAL SYSTEM
    Cranking Motor (Heavy Duty, Positive Engagement) ..............................................................................................—  volt      24
    Battery Charging System, Negative Ground ..................................................................................................... — ampere         35
    Maximum Allowable Resistance of Cranking Circuit.................................................................................................— ohm      0.002
    Minimum Recommended Battery Capacity
    • Cold Soak @ 50°F (10 °C) and Above ........................................................................................................—0°F CCA       1280
    • Cold Soak @ 32°F to 50 °F (0 °C to 10 °C)................................................................................................—0°F CCA       1800
    • Cold Soak @ 0 °F to 32 °F (-18 °C to 0 °C)................................................................................................—0°F CCA     1800
    COLD START CAPABILITY
    Minimum Ambient Temperature for Aided (with Coolant Heater) Cold Start within 10 seconds................................—°F (°C)      50      (10)
    Minimum Ambient Temperature for Unaided Cold Start............................................................................................—°F (°C)      45   (7)
    PERFORMANCE DATA
    All data is based on: • Engine operating with fuel system, water pump, lubricating oil pump, air cleaner and exhaust
                           silencer; not included are battery charging alternator, fan, and optional driven components.
                         • Engine operating with fuel corresponding to grade No. 2-D per ASTM D975.
                         • ISO 3046, Part 1, Standard Reference Conditions of:
                         Barometric Pressure :  100 kPa (29.53 in Hg) Air Temperature : 25 °C (77 °F)
                         Altitude :  110 m (361 ft) Relative Humidity : 30%
     
    Steady State Stability Band at any Constant Load ............................................................................................................—%      +/- 0.25
    Estimated Free Field Sound Pressure Level of a Typical Generator Set; .
    Excludes Exhaust Noise; at Rated Load and 7.5 m (24.6 ft); 1800 rpm / 1500 rpm.......................................................—dBA     94.6 / 92.4
    Exhaust Noise at 1 m Horizontally from Centerline of Exhaust Pipe Outlet Upwards at 45°   —  1800 / 1500 rpm....—dBA     126 / 125
     
                                                                         STANDBYPOWER   PRIME POWERUNLIMITED TIME
                                                                            60 hz      50 hz      60 hz          50 hz
    Governed Engine peed....................................................................—rpm        1800         1500       1800        1500
    Engine Idle Speed ......................................................................... —rpm      725 - 775      725 - 775      725 - 775    725 - 775
    Gross Engine Power Output. .................................................BHP (kWm)   1850 (1380)   1645  (1227)   1635  (1220)   1470  (1097)
    Brake Mean Effective Pressure ...........................................—  psi (kPa)    265 (1827)    283  (1951)    235  (1620)    253  (1744)
    Piston Speed................................................................—  ft / min (m / s)    1875  (9.5)      1562  (7.9)    1875  (9.5)   1562  (7.9)
    Friction Horsepower ............................................................... HP (kWm)     225  (168)      155  (116)     225  (168)    155  (116)
    Engine Water Flow at Stated Friction Head External to Engine:         
    • 4 psi Friction Head..............................................—  US gpm (liter / s)     535 (33.7)    440 (27.8)     535  (33.7)    440  (27.8)
    • Maximum Friction Head......................................—  US gpm (liter / s)     470 (29.6)      400 (25.2)     470  (29.6)    400  (25.2)
     
    Engine Data with Dry Type Exhaust Manifold
    Intake Air Flow ..............................................................—  cfm (liter / s)    3900 (1840)    3700 (1746)   3700  (1746)   3400  (1605)
    Exhaust Gas Temperature................................................   —  °F (°C)     887 (475)       977  (525)    860  (460)     968  (520)
    Exhaust Gas Flow ........................................................—  cfm (liter / s)    9100 (4295)    8500 (4011)   8400  (3964)   7900  (3728)
    Air to Fuel Ratio ..................................................................—  air : fuel       26.5 : 1       27.0 : 1       27.5 : 1       28.0 : 1
    Radiated Heat to Ambient ....................................—  BTU / min (kWm)   10000  (176)     8500 (150)    8500  (150)    7300  (130)
    Heat Rejection to Coolant ...................................—  BTU / min (kWm)    51000 (900)     44000 (775)   44000  (775)   38500  (680)
    Heat Rejection to Exhaust...................................—  BTU / min (kWm)    53000 (935)     48000 (845)    47000  (830)   43000  (760)
     
    N.A.  - Data is Not Available
    N/A- Not Applicable to this Engine
    TBD  - To Be Determined
                                                                                       ENGINE MODEL : KTA50-G3
                                                                                          DATA SHEET :DS-6250
    CUMMINS ENGINE COMPANY, INC.             Columbus, Indiana 47202-3005            DATE :12Jan01
                                                                                                CURVE NO. : FR-6250
     
              KTA50-G3 Derate Curves @ 1800 RPM                 CURVE NO : FR-6250
     
    图片1.png                                                                                                
    DATE : 12Jan01
     
     
     
     
     
                   NOTE:Derates shown are based on 15 in H20 air intake restriction and 2 in Hg exhaust back pressure.
                   For sustained operation above these conditions, derate by an additional 6% per 1000 ft (300 m) and 8% per 18° F (10° C).
     
     
     
    Reference Standards:
      BS-5514 and DIN-6271 standards are based on ISO-3046.
     
     

     


     

    技术通报的翻译和出版等组织管理工作由康明斯动力设备(深圳)有限公司培训中心承担,我们的目标是及时提供、更新康明斯产品的技术通报,帮助客户使用和维护保养好发动机,同时积极支援新机型的推广及应用。

    目前已翻译出版的文献资料达到150余种。这些资料包括:维护保养手册、故障排除手册、大修手册、补救修理手册、零件目录、各种产品的介绍文献、服务零件简报等。此外,还有20余种教学光盘。

    康明斯公司组合图.png

    了解更多柴油发电机组的技术资料及详细参数请登录康明斯官方网站:www.cms-power.com

  • 上一篇:450KW重庆康明斯静音柴油机技术参数
  • 下一篇:400KW重庆康明斯静音柴油机技术参数
  • 相关资讯推荐